PUE tables copper conductors wires cables. Permissible long-term currents for wires, cords and cables with rubber or plastic insulation. Wiring quality and aging

When repairing and designing electrical equipment, it becomes necessary to choose the right wires. You can use a special calculator or reference book. But for this you need to know the load parameters and cable laying features.

Why do you need to calculate the cable cross-section?

The following requirements apply to electrical networks:

  • safety;
  • reliability;
  • efficiency.

If the selected cross-sectional area of ​​the wire is small, then the current loads on the cables and wires will be large, which will lead to overheating. As a result, an emergency may occur that will damage all electrical equipment and become dangerous to the life and health of people.

If you install wires with a large cross-sectional area, then safe use is ensured. But from a financial point of view there will be cost overruns. The correct choice of wire cross-section is the key to long-term safe operation and rational use of financial resources.

The cable cross-section is calculated based on power and current. Let's look at examples. To determine what wire cross-section is needed for 5 kW, you will need to use the PUE tables (“Electrical Installation Rules”). This directory is a regulatory document. It states that the choice of cable cross-section is made according to 4 criteria:

  1. Supply voltage (single-phase or three-phase).
  2. Conductor material.
  3. Load current, measured in amperes (A), or power - in kilowatts (kW).
  4. Cable location.

The PUE does not have a value of 5 kW, so you will have to choose the next larger value - 5.5 kW. For installation in an apartment today it is necessary to use copper wire. In most cases, installation is by air, so a cross-section of 2.5 mm² is suitable from the reference tables. In this case, the maximum permissible current load will be 25 A.

The above reference book also regulates the current for which the input circuit breaker (VA) is designed. According to the “Electrical Installation Rules”, with a load of 5.5 kW, the VA current should be 25 A. The document states that the rated current of the wire that is suitable for a house or apartment should be an order of magnitude greater than that of the VA. In this case, after 25 A there is 35 A. The last value must be taken as the calculated one. A current of 35 A corresponds to a cross section of 4 mm² and a power of 7.7 kW. So, the choice of the cross-section of the copper wire according to power is completed: 4 mm².

To find out what wire cross-section is needed for 10 kW, we will again use the reference book. If we consider the case for open wiring, then we need to decide on the cable material and the supply voltage. For example, for an aluminum wire and a voltage of 220 V, the nearest higher power will be 13 kW, the corresponding cross-section is 10 mm²; for 380 V the power will be 12 kW and the cross-section will be 4 mm².

Choose by power

Before choosing a cable cross-section based on power, you need to calculate its total value and make a list of electrical appliances located in the territory to which the cable is laid. The power must be indicated on each device; the corresponding units of measurement will be written next to it: W or kW (1 kW = 1000 W). Then you will need to add up the power of all equipment and get the total.

If you select a cable to connect one device, then only information about its energy consumption is sufficient. You can select wire cross-sections based on power in the PUE tables.

Table 1. Selection of wire cross-section based on power for cables with copper conductors

For cable with copper conductors
Voltage 220 VVoltage 380 V
Current, Apower, kWtCurrent, Apower, kWt
1,5 19 4,1 16 10,5
2,5 27 5,9 25 16,5
4 38 8,3 30 19,8
6 46 10,1 40 26,4
10 70 15,4 50 33
16 85 18,7 75 49,5
25 115 25,3 90 59,4
35 135 29,7 115 75.9
50 175 38.5 145 95,7
70 215 47,3 180 118,8
95 260 57,2 220 145,2
120 300 66 260 171,6

Table 2. Selection of wire cross-section based on power for cables with aluminum conductors

Conductor cross-section, mm²For cable with aluminum conductors
Voltage 220 VVoltage 380 V
Current, Apower, kWtCurrent, Apower, kWt
2,5 20 4,4 19 12,5
4 28 6,1 23 15,1
6 36 7,9 30 19,8
10 50 11,0 39 25,7
16 60 13,2 55 36,3
25 85 18,7 70 46,2
35 100 22,0 85 56,1
50 135 29,7 110 72,6
70 165 36,3 140 92,4
95 200 44,0 170 112,2
120 230 50,6 200 132,2

In addition, you need to know the network voltage: three-phase corresponds to 380 V, and single-phase - 220 V.

The PUE provides information for both aluminum and copper wires. Both have their advantages and disadvantages. Advantages of copper wires:

  • high strength;
  • elasticity;
  • oxidation resistance;
  • electrical conductivity is greater than that of aluminum.

The disadvantage of copper conductors is their high cost. In Soviet houses, aluminum electrical wiring was used during construction. Therefore, if a partial replacement occurs, it is advisable to install aluminum wires. The only exceptions are those cases when new wiring is installed instead of all the old wiring (up to the switchboard). Then it makes sense to use copper. It is unacceptable for copper and aluminum to come into direct contact, as this leads to oxidation. Therefore, a third metal is used to connect them.

You can independently calculate the wire cross-section according to power for a three-phase circuit. To do this, you need to use the formula: I=P/(U*1.73), where P – power, W; U – voltage, V; I – current, A. Then the cable cross-section is selected from the reference table depending on the calculated current. If the required value is not there, then the closest one is selected, which exceeds the calculated one.

How to calculate by current

The amount of current passing through a conductor depends on the length, width, resistivity of the latter and on temperature. When heated, the electric current decreases. Reference information is given for room temperature (18°C). To select the cable cross-section for current, use the PUE tables.

Table3. Electric current for copper wires and cords with rubber and PVC insulation

Conductor cross-sectional area, mm²
openin one pipe
two single-corethree single-corefour single-coreone two-wireone three-wire
0,5 11 - - - - -
0,75 15 - - - - -
1 17 16 15 14 15 14
1,2 20 18 16 15 16 14,5
1,5 23 19 17 16 18 15
2 26 24 22 20 23 19
2,5 30 27 25 25 25 21
3 34 32 28 26 28 24
4 41 38 35 30 32 27
5 46 42 39 34 37 31
6 50 46 42 40 40 34
8 62 54 51 46 48 43
10 80 70 60 50 55 50
16 100 85 80 75 80 70
25 140 115 100 90 100 85
35 170 135 125 115 125 100
50 215 185 170 150 160 135
70 270 225 210 185 195 175
95 330 275 255 225 245 215
120 385 315 290 260 295 250
150 440 360 330 - - -
185 510 - - - - -
240 605 - - - - -
300 695 - - - - -
400 830 - - - - -

A table is used to calculate aluminum wires.

Table4. Electric current for aluminum wires and cords with rubber and PVC insulation

Conductor cross-sectional area, mm²Current, A, for wires laid
openin one pipe
two single-corethree single-corefour single-coreone two-wireone three-wire
2 21 19 18 15 17 14
2,5 24 20 19 19 19 16
3 27 24 22 21 22 18
4 32 28 28 23 25 21
5 36 32 30 27 28 24
6 39 36 32 30 31 26
8 46 43 40 37 38 32
10 60 50 47 39 42 38
16 75 60 60 55 60 55
25 105 85 80 70 75 65
35 130 100 95 85 95 75
50 165 140 130 120 125 105
70 210 175 165 140 150 135
95 255 215 200 175 190 165
120 295 245 220 200 230 190
150 340 275 255 - - -
185 390 - - - - -
240 465 - - - - -
300 535 - - - - -
400 645 - - - - -

In addition to the electric current, you will need to select the conductor material and voltage.

For an approximate calculation of the cable cross-section for current, it must be divided by 10. If the resulting cross-section is not in the table, then it is necessary to take the nearest larger value. This rule is only suitable for cases where the maximum permissible current for copper wires does not exceed 40 A. For the range from 40 to 80 A, the current must be divided by 8. If aluminum cables are installed, then it must be divided by 6. This is because for To ensure equal loads, the thickness of the aluminum conductor is greater than that of copper.

Calculation of cable cross-section by power and length

The cable length affects the voltage loss. Thus, at the end of the conductor the voltage may decrease and become insufficient for the operation of the electrical appliance. For household electrical networks, these losses can be neglected. It will be enough to take a cable 10-15 cm longer. This reserve will be used for switching and connection. If the ends of the wire are connected to the shield, then the spare length should be even greater, since circuit breakers will be connected.

When laying cables over long distances, voltage drop must be taken into account. Each conductor is characterized by electrical resistance. This parameter is affected by:

  1. Wire length, unit of measurement – ​​m. As it increases, losses increase.
  2. Cross-sectional area, measured in mm². As it increases, the voltage drop decreases.
  3. Material resistivity (reference value). Shows the resistance of a wire measuring 1 square millimeter per 1 meter.

The voltage drop is numerically equal to the product of resistance and current. It is acceptable that the specified value does not exceed 5%. Otherwise, you need to take a cable with a larger cross-section. Algorithm for calculating wire cross-section based on maximum power and length:

  1. Depending on the power P, voltage U and cosph coefficient, we find the current using the formula: I=P/(U*cosph). For electrical networks that are used in everyday life, cosф = 1. In industry, cosф is calculated as the ratio of active power to total power. The latter consists of active and reactive powers.
  2. Using PUE tables, the current cross-section of the wire is determined.
  3. We calculate the resistance of the conductor using the formula: Ro=ρ*l/S, where ρ is the resistivity of the material, l is the length of the conductor, S is the cross-sectional area. It is necessary to take into account the fact that current flows through the cable not only in one direction, but also back. Therefore, the total resistance: R = Ro*2.
  4. We find the voltage drop from the relationship: ΔU=I*R.
  5. We determine the voltage drop as a percentage: ΔU/U. If the obtained value exceeds 5%, then select the nearest larger cross-section of the conductor from the reference book.

Open and closed wiring

Depending on the placement, wiring is divided into 2 types:

  • closed;
  • open.

Today, hidden wiring is installed in apartments. Special recesses are created in the walls and ceilings to accommodate cables. After installing the conductors, the recesses are plastered. Copper wires are used. Everything is planned in advance, because over time, to build up electrical wiring or replace elements, you will have to dismantle the finishing. For hidden finishing, wires and cables that have a flat shape are often used.

When laid open, the wires are installed along the surface of the room. Advantages are given to flexible conductors that have a round shape. They are easy to install in cable channels and pass through the corrugation. When calculating the load on the cable, the method of laying the wiring is taken into account.

Cable power table required to correctly calculate the cable cross-section, if the power of the equipment is large and the cable cross-section is small, then it will heat up, which will lead to the destruction of the insulation and loss of its properties.

To calculate the conductor resistance, you can use the conductor resistance calculator.

For the transmission and distribution of electric current, the main means are cables; they ensure the normal operation of everything related to electric current, and how good this work will be depends on the right choice cable cross-section by power. A convenient table will help you make the necessary selection:

Current cross-section
conductive
lived mm

Voltage 220V

Voltage 380V

Current. A

Power. kW

Current. A

Power, kWt

Section

Toko-
conductive
lived mm

Aluminum conductors wires and cables

Voltage 220V

Voltage 380V

Current. A

Power. kW

Current. A

Power, kWt

But in order to use the table, you need to calculate the total power consumption of devices and equipment that are used in a house, apartment or other place where the cable will be laid.

Example of power calculation.

Let's say you are installing closed electrical wiring in a house using an explosive cable. You need to write down a list of equipment used on a piece of paper.

But how now find out power? You can find it on the equipment itself, where there is usually a label with the main characteristics recorded.

Power is measured in Watts (W, W) or Kilowatts (kW, KW). Now you need to write down the data and then add it up.

The resulting number is, for example, 20,000 W, which would be 20 kW. This figure shows how much energy all electrical receivers together consume. Next, you should consider how many devices will be used simultaneously over a long period of time. Let’s say it turns out to be 80%, in which case the simultaneity coefficient will be equal to 0.8. We calculate the cable cross-section based on power:

20 x 0.8 = 16 (kW)

To select a cross-section, you will need a cable power table:

Current cross-section
conductive
lived mm

Copper conductors of wires and cables

Voltage 220V

Voltage 380V

Current. A

Power. kW

Current. A

Power, kWt

10

15.4

If the three-phase circuit is 380 Volts, then the table will look like this:

Current cross-section
conductive
lived mm

Copper conductors of wires and cables

Voltage 220V

Voltage 380V

Current. A

Power. kW

Current. A

Power, kWt

16.5

10

15.4

These calculations are not particularly difficult, but it is recommended to choose a wire or cable with the largest cross-section of conductors, because it may be that it will be necessary to connect some other device.

Additional cable power table.

When installing electrical wiring, it is necessary to determine the power of consumers in advance. This will help in the optimal selection of cables. This choice will allow you to operate the wiring for a long time and safely without repairs.

Cable and conductor products are very diverse in their properties and intended purpose, and also have a wide range in prices. The article talks about the most important wiring parameter - the cross-section of a wire or cable in terms of current and power, and how to determine the diameter - calculate it using a formula or select it using a table.

The current-carrying part of the cable is made of metal. The part of the plane passing at right angles to the wire, bounded by metal, is called wire cross-section. The unit of measurement is square millimeters.

Section determines permissible currents passing through wires and cables. This current, according to the Joule-Lenz law, leads to the release of heat (proportional to the resistance and the square of the current), which limits the current.

Conventionally, three temperature ranges can be distinguished:

  • the insulation remains intact;
  • the insulation burns, but the metal remains intact;
  • metal melts at high temperatures.

Of these, only the first is the permissible operating temperature. In addition, with a decrease in cross-section its electrical resistance increases, which leads to an increase in voltage drop in the wires.

However, an increase in cross-section leads to an increase in mass and especially cost or cable.

The materials used for the industrial production of cable products are pure copper or aluminum. These metals have different physical properties, in particular resistivity, and therefore the cross sections selected for a given current may be different.

Find out from this video how to choose the correct wire or cable cross-section according to power for home wiring:

Determination and calculation of cores using the formula

Now let’s figure out how to correctly calculate the cross-section of a wire based on power, knowing the formula. Here we will solve the problem of determining the section. It is the cross section that is the standard parameter due to the fact that the nomenclature includes both single-core and multi-core options. The advantage of multi-core cables is their greater flexibility and resistance to kinks during installation. As a rule, stranded wires are made of copper.

The easiest way to determine the cross-section of a round single-core wire is d– diameter, mm; S– area in square millimeters:

Stranded ones are calculated by a more general formula: n– number of veins, d– core diameter, S- square:

The diameter of the core can be determined by removing the insulation and measuring the diameter against the bare metal with a caliper or micrometer.

The current density is determined very simply, it is number of amperes per section. There are two wiring options: open and closed. The open one allows for a higher current density due to better heat transfer to the environment. Closed requires a downward adjustment so that the heat balance does not lead to overheating in the tray, cable duct or shaft, which can cause a short circuit or even a fire.

Accurate thermal calculations are very complex; in practice, they are based on the permissible operating temperature of the most critical element in the structure, according to which the current density is selected.

Thus, the permissible current density is the value at which heating of the insulation of all wires in a bundle (cable duct) remains safe, taking into account the maximum ambient temperature.

Table of current cross-section of copper and aluminum wire or cable:

Table 1 shows the permissible current density for temperatures not higher than room temperature. Most modern wires have PVC or polyethylene insulation, allowing heating during operation no more than 70-90°C. For “hot” rooms, the current density must be reduced by a factor of 0.9 for every 10°C to the operating temperatures of the wires or cables.

Now about what is considered open and what . is wiring if it is made with clamps (tires) along the walls, ceiling, along the supporting cable or through the air. The closed one is laid in cable trays, walled into walls under plaster, made in pipes, a shell or laid in the ground. You should also consider the wiring closed if it is in or. The closed one cools worse.

For example, let the thermometer in the dryer room show 50°C. To what value should the current density of a copper cable laid in this room along the ceiling be reduced if the cable insulation can withstand heating up to 90°C? The difference is 50-20 = 30 degrees, which means you need to use the coefficient three times. Answer:

Example of calculating the wiring section and load

Let the suspended ceiling be illuminated by six lamps with a power of 80 W each and they are already connected to each other. We need to supply power to them using aluminum cable. We will assume that the wiring is closed, the room is dry, and the temperature is room temperature. Now we’ll find out how to calculate the power of copper and aluminum cables; for this we use the equation that determines the power (according to the new standards, we consider the mains voltage to be equal to 230 V):

Using the corresponding current density for aluminum from Table 1, we find the cross section required for the line to operate without overheating:

If we need to find the diameter of the wire, we use the formula:

Suitable would be cable APPV2x1.5 (section 1.5 mm.kv). This is perhaps the thinnest cable you can find on the market (and one of the cheapest). In the above case, it provides a double power reserve, i.e. a consumer with a permissible load power of up to 500 W, for example, a fan, dryer or additional lamps, can be installed on this line.

It is unacceptable to install sockets on this line, since they may (and most likely will) contain a powerful consumer and this will lead to overloading the line section.

Quick selection: useful standards and ratios

To save time, calculations are usually tabulated, especially since the range of cable products is quite limited. The following table shows the calculation of the cross-section of copper and aluminum wires according to power consumption and current strength, depending on the purpose - for open and closed wiring. The diameter is obtained as a function of load power, metal and type of wiring. The mains voltage is considered to be 230 V.

The table allows you to quickly select a section or diameter, if the load power is known. The found value is rounded up to the nearest value from the nomenclature series.

The following table summarizes the data on permissible currents by cross-section and power of materials of cables and wires for calculation and quick selection of the most suitable ones:

The wiring arrangement, among other things, requires design skills, which not everyone who wants to do it has. It is not enough to just have good electrical installation skills. Some people confuse design with drawing up documentation according to some rules. These are completely different things. A good project can be written out on pieces of paper from a notebook.

First of all, draw a plan of your premises and mark future sockets and lamps. Find out the power of all your consumers: irons, lamps, heating devices, etc. Then enter the power of the loads most frequently consumed in different rooms. This will allow you to choose the best cable options.

You will be surprised how many possibilities there are and what is the reserve for saving money. Once you select , count the length of each line you draw. Put everything together, and then you will get exactly what you need, and as much as you need.

Each line must be protected by its own (), designed for a current corresponding to the permissible power of the line (the sum of the consumer powers). Sign the machines, located in, for example: “kitchen”, “living room”, etc.

It is advisable to have a separate line for all lighting, then you can easily repair the socket in the evening without using matches. It is the sockets that are most often overloaded. Provide outlets with enough power - you don't know in advance what you'll have to plug into them.

In damp rooms, use only double-insulated cables! Use modern sockets (“Euro”) and with grounding conductors and connect the grounding correctly. Bend single-core wires, especially copper ones, smoothly, leaving a radius of several centimeters. This will prevent them from breaking. Wires must lie straight in cable trays and ducts, but freely, in no case should you pull them like a string.

There should be a margin of a few extra centimeters. When laying, you need to make sure that there are no sharp corners anywhere that could cut the insulation. The terminals must be tightened tightly when connecting., and for stranded wires this procedure should be repeated; they have a tendency for the cores to shrink, as a result of which the connection may become loose.

Copper wires and aluminum wires are not “friendly” with each other for electrochemical reasons; they cannot be connected directly. To do this, you can use special terminal blocks or galvanized washers. The joints must always be dry.

Phase conductors must be white (or brown), and neutrals must always be blue. Grounding is yellow-green in color. These are generally accepted color rules and commercial cables, as a rule, have internal insulation in exactly these colors. Compliance with colors increases the safety of operation and repair.

We bring to your attention an interesting and educational video on how to correctly calculate the cable cross-section by power and length:

The choice of wire cross-section is the main element of a power supply project of any scale, from a room to large networks. The current that can be taken into the load and power will depend on this. The correct choice of wires also ensures electrical and fire safety, and provides an economical budget for your project.

1.3.1. This chapter of the Rules applies to the selection of cross-sections of electrical conductors (bare and insulated wires, cables and buses) for heating, economic current density and corona conditions. If the cross-section of the conductor determined according to these conditions is less than the cross-section required by other conditions (thermal and electrodynamic resistance to short-circuit currents, voltage losses and deviations, mechanical strength, overload protection), then the largest cross-section required by these conditions should be accepted.

Selection of heating conductor cross-sections

1.3.2. Conductors for any purpose must meet the requirements for maximum permissible heating, taking into account not only normal, but also post-emergency conditions, as well as conditions during repairs and possible uneven current distribution between lines, bus sections, etc. When checking for heating, a half-hour maximum is accepted current, the largest of the average half-hour currents of a given network element.

1.3.3. For intermittent and short-term operating modes of electrical receivers (with a total cycle duration of up to 10 minutes and an operating period of no more than 4 minutes), the current reduced to the long-term mode should be taken as the calculated current for checking the cross-section of heating conductors. Wherein:

1) for copper conductors with a cross-section of up to 6 mm², and for aluminum conductors up to 10 mm², the current is taken as for installations with long-term operation;

2) for copper conductors with a cross-section of more than 6 mm², and for aluminum conductors with a cross-section of more than 10 mm², the current is determined by multiplying the permissible continuous current by the coefficient, where Tpk- the duration of the working period expressed in relative units (the duration of switching on in relation to the duration of the cycle).

1.3.4. For a short-term operating mode with a switching duration of no more than 4 minutes and breaks between switching on sufficient to cool the conductors to ambient temperature, the maximum permissible currents should be determined according to the standards for repeated short-term duty (see 1.3.3). When the duration of switching on is more than 4 minutes, as well as during breaks of insufficient duration between switching on, the maximum permissible currents should be determined as for installations with a long operating mode.

1.3.5. For cables with voltages up to 10 kV with impregnated paper insulation that carry less than rated loads, a short-term overload indicated in table may be allowed. 1.3.1.

1.3.6. For the period of liquidation of the post-emergency regime, an overload of up to 10% is allowed for cables with polyethylene insulation, and for cables with polyvinyl chloride insulation up to 15% of the rated load during maximum loads lasting no more than 6 hours per day for 5 days, if the load during the remaining periods of time of these days does not exceed the nominal.

During the period of liquidation of the post-emergency regime, overloads are allowed for 5 days for cables with voltages up to 10 kV with paper insulation. within the limits specified in table. 1.3.2.

Table 1.3.1. Permissible short-term overload for cables with voltages up to 10 kV with impregnated paper insulation

Table 1.3.2. Permissible overload for the period of post-emergency liquidation for cables with voltage up to 10 kV with paper insulation

For cable lines that have been in operation for more than 15 years, overloads should be reduced by 10%.

Overloading cable lines with a voltage of 20-35 kV is not allowed.

1.3.7. The requirements for normal loads and post-accident overloads apply to cables and the connecting and termination couplings and terminations installed on them.

1.3.8. Zero working conductors in a four-wire three-phase current system must have a conductivity of at least 50% of the conductivity of the phase conductors; if necessary, it should be increased to 100% of the conductivity of the phase conductors.

1.3.9. When determining permissible long-term currents for cables, bare and insulated wires and busbars, as well as for rigid and flexible conductors laid in an environment whose temperature differs significantly from that given in 1.3.12-1.3.15 and 1.3.22, coefficients should be applied, given in table. 1.3.3.

Table 1.3.3. Correction factors for currents for cables, bare and insulated wires and busbars depending on ground and air temperatures

Conditional ambient temperature, °C Standardized core temperature, °C Correction factors for currents at the design temperature of the environment, °C
-5 and below 0 +5 +10 +15 +20 +25 +30 +35 +40 +45 +50
15 80 1,14 1,11 1,08 1,04 1,00 0,96 0,92 0,88 0,83 0,78 0,73 0,68
25 80 1,24 1,20 1,17 1,13 1,09 1,04 1,00 0,95 0,90 0,85 0,80 0,74
25 70 1,29 1,24 1,20 1,15 1,11 1,05 1,00 0,94 0,88 0,81 0,74 0,67
15 65 1,18 1,14 1,10 1,05 1,00 0,95 0,89 0,84 0,77 0,71 0,63 0,55
25 65 1,32 1,27 1,22 1,17 1,12 1,06 1,00 0,94 0,87 0,79 0,71 0,61
15 60 1,20 1,15 1,12 1,06 1,00 0,94 0,88 0,82 0,75 0,67 0,57 0,47
25 60 1,36 1,31 1,25 1,20 1,13 1,07 1,00 0,93 0,85 0,76 0,66 0,54
15 55 1,22 1,17 1,12 1,07 1,00 0,93 0,86 0,79 0,71 0,61 0,50 0,36
25 55 1,41 1,35 1,29 1,23 1,15 1,08 1,00 0,91 0,82 0,71 0,58 0,41
15 50 1,25 1,20 1,14 1,07 1,00 0,93 0,84 0,76 0,66 0,54 0,37 -
25 50 1,48 1,41 1,34 1,26 1,18 1,09 1,00 0,89 0,78 0,63 0,45 -

Permissible long-term stress for wires, cords and cables with rubber or plastic insulation

1.3.10. Permissible long-term currents for wires with rubber or polyvinyl chloride insulation, cords with rubber insulation and cables with rubber or plastic insulation in lead, polyvinyl chloride and rubber sheaths are given in Table. 1.3.4-1.3.11. They are accepted for temperatures: cores +65, ambient air +25 and ground + 15°C.

When determining the number of wires laid in one pipe (or cores of a stranded conductor), the neutral working conductor of a four-wire three-phase current system, as well as grounding and neutral protective conductors are not taken into account.

Permissible long-term currents for wires and cables laid in boxes, as well as in trays in bundles, must be accepted: for wires - according to table. 1.3.4 and 1.3.5 as for wires laid in pipes, for cables - according to table. 1.3.6-1.3.8 as for cables laid in the air. If the number of simultaneously loaded wires is more than four, laid in pipes, boxes, and also in trays in bundles, the currents for the wires should be taken according to the table. 1.3.4 and 1.3.5 as for wires laid openly (in the air), with the introduction of reduction factors of 0.68 for 5 and 6; 0.63 for 7-9 and 0.6 for 10-12 conductors.

For secondary circuit wires, reduction factors are not introduced.

Table 1.3.4. Permissible continuous current for wires and cords with rubber and polyvinyl chloride insulation with copper conductors

open in one pipe
two single-core three single-core four single-core one two-wire one three-wire
0,5 11 - - - - -
0,75 15 - - - - -
1 17 16 15 14 15 14
1,2 20 18 16 15 16 14,5
1,5 23 19 17 16 18 15
2 26 24 22 20 23 19
2,5 30 27 25 25 25 21
3 34 32 28 26 28 24
4 41 38 35 30 32 27
5 46 42 39 34 37 31
6 50 46 42 40 40 34
8 62 54 51 46 48 43
10 80 70 60 50 55 50
16 100 85 80 75 80 70
25 140 115 100 90 100 85
35 170 135 125 115 125 100
50 215 185 170 150 160 135
70 270 225 210 185 195 175
95 330 275 255 225 245 215
120 385 315 290 260 295 250
150 440 360 330 - - -
185 510 - - - - -
240 605 - - - - -
300 695 - - - - -
400 830 - - - - -

Table 1.3.5. Permissible continuous current for rubber and polyvinyl chloride insulated wires with aluminum conductors

Conductor cross-section, mm² Current, A, for wires laid
open in one pipe
two single-core three single-core four single-core one two-wire one three-wire
2 21 19 18 15 17 14
2,5 24 20 19 19 19 16
3 27 24 22 21 22 18
4 32 28 28 23 25 21
5 36 32 30 27 28 24
6 39 36 32 30 31 26
8 46 43 40 37 38 32
10 60 50 47 39 42 38
16 75 60 60 55 60 55
25 105 85 80 70 75 65
35 130 100 95 85 95 75
50 165 140 130 120 125 105
70 210 175 165 140 150 135
95 255 215 200 175 190 165
120 295 245 220 200 230 190
150 340 275 255 - - -
185 390 - - - - -
240 465 - - - - -
300 535 - - - - -
400 645 - - - - -

Table 1.3.6. Permissible continuous current for wires with copper conductors with rubber insulation in metal protective sheaths and cables with copper conductors with rubber insulation in lead, polyvinyl chloride, nayrite or rubber sheaths, armored and unarmored

Conductor cross-section, mm² Current *, A, for wires and cables
single-core two-wire three-wire
when laying
in the air in the air in the ground in the air in the ground
__________________

* Currents apply to wires and cables both with and without a neutral core.

1,5 23 19 33 19 27
2,5 30 27 44 25 38
4 41 38 55 35 49
6 50 50 70 42 60
10 80 70 105 55 90
16 100 90 135 75 115
25 140 115 175 95 150
35 170 140 210 120 180
50 215 175 265 145 225
70 270 215 320 180 275
95 325 260 385 220 330
120 385 300 445 260 385
150 440 350 505 305 435
185 510 405 570 350 500
240 605 - - - -

Table 1.3.7. Permissible continuous current for cables with aluminum conductors with rubber or plastic insulation in lead, polyvinyl chloride and rubber sheaths, armored and unarmored

Conductor cross-section, mm² Current, A, for cables
single-core two-wire three-wire
when laying
in the air in the air in the ground in the air in the ground
2,5 23 21 34 19 29
4 31 29 42 27 38
6 38 38 55 32 46
10 60 55 80 42 70
16 75 70 105 60 90
25 105 90 135 75 115
35 130 105 160 90 140
50 165 135 205 110 175
70 210 165 245 140 210
95 250 200 295 170 255
120 295 230 340 200 295
150 340 270 390 235 335
185 390 310 440 270 385
240 465 - - - -

Note. Permissible continuous currents for four-core cables with plastic insulation for voltages up to 1 kV can be selected according to table. 1.3.7, as for three-core cables, but with a coefficient of 0.92.

Table 1.3.8. Permissible continuous current for portable light and medium hose cords, portable heavy duty hose cables, mine flexible hose cables, floodlight cables and portable wires with copper conductors

Conductor cross-section, mm² Current *, A, for cords, wires and cables
single-core two-wire three-wire
__________________

* Currents apply to cords, wires and cables with and without a neutral core.

0,5 - 12 -
0,75 - 16 14
1,0 - 18 16
1,5 - 23 20
2,5 40 33 28
4 50 43 36
6 . 65 55 45
10 90 75 60
16 120 95 80
25 160 125 105
35 190 150 130
50 235 185 160
70 290 235 200

Table 1.3.9. Permissible continuous current for portable hose cables with copper conductors and rubber insulation for peat enterprises

Table 1.3.10. Permissible continuous current for hose cables with copper conductors and rubber insulation for mobile electrical receivers

Table 1.3.11. Permissible continuous current for wires with copper conductors with rubber insulation for electrified transport 1.3 and 4 kV

Conductor cross-section, mm² Current, A Conductor cross-section, mm² Current, A Conductor cross-section, mm² Current, A
1 20 16 115 120 390
1,5 25 25 150 150 445
2,5 40 35 185 185 505
4 50 50 230 240 590
6 65 70 285 300 670
10 90 95 340 350 745

Table 1.3.12. Reduction factor for wires and cables laid in boxes

Laying method Number of laid wires and cables Reduction factor for power supply wires
single-core stranded separate electrical receivers with a utilization factor of up to 0.7 groups of electrical receivers and individual receivers with a utilization factor of more than 0.7
Multilayered and bundled - Up to 4 1,0 -
2 5-6 0,85 -
3-9 7-9 0,75 -
10-11 10-11 0,7 -
12-14 12-14 0,65 -
15-18 15-18 0,6 -
Single layer 2-4 2-4 - 0,67
5 5 - 0,6

1.3.11. Permissible long-term currents for wires laid in trays, when laid single-row (not in bundles), should be taken as for wires laid in the air.

Permissible long-term currents for wires and cables laid in boxes should be taken according to table. 1.3.4-1.3.7 as for single wires and cables laid openly (in the air), using the reduction factors indicated in table. 1.3.12.

When choosing reduction factors, control and reserve wires and cables are not taken into account.

Permissible continuous currents for cables with impregnated paper insulation

1.3.12. Permissible continuous currents for cables with voltages up to 35 kV with insulation made of impregnated cable paper in a lead, aluminum or polyvinyl chloride sheath are accepted in accordance with the permissible temperatures of the cable cores:

1.3.13. For cables laid in the ground, permissible long-term currents are given in table. 1.3.13, 1.3.16, 1.3.19-1.3.22. They are taken on the basis of laying no more than one cable in a trench at a depth of 0.7-1.0 m at a ground temperature of +15°C and a ground resistivity of 120 cm K/W.

Table 1.3.13. Permissible long-term current for cables with copper conductors with paper impregnated with oil rosin and non-drip insulation in a lead sheath, laid in the ground

Conductor cross-section, mm² Current, A, for cables
single-core up to 1 kV two-wire up to 1 kV three-wire voltage, kV four-wire up to 1 kV
until 3 6 10
6 - 80 70 - - -
10 140 105 95 80 - 85
16 175 140 120 105 95 115
25 235 185 160 135 120 150
35 285 225 190 160 150 175
50 360 270 235 200 180 215
70 440 325 285 245 215 265
95 520 380 340 295 265 310
120 595 435 390 340 310 350
150 675 500 435 390 355 395
185 755 - 490 440 400 450
240 880 - 570 510 460 -
300 1000 - - - - -
400 1220 - - - - -
500 1400 - - - - -
625 1520 - - - - -
800 1700 - - - - -

Table 1.3.14. Permissible continuous current for cables with copper conductors with paper impregnated with oil rosin and non-drip insulation in a lead sheath, laid in water

Conductor cross-section, mm² Current, A, for cables
three-wire voltage, kV four-wire up to 1 kV
until 3 6 10
16 - 135 120 -
25 210 170 150 195
35 250 205 180 230
50 305 255 220 285
70 375 310 275 350
95 440 375 340 410
120 505 430 395 470
150 565 500 450 -
185 615 545 510 -
240 715 625 585 -

Table 1.3.15. Permissible continuous current for cables with copper conductors with paper impregnated with oil rosin and non-drip insulation in a lead sheath, laid in the air

Conductor cross-section, mm² Current, A, for cables
single-core up to 1 kV two-wire up to 1 kV three-wire voltage, kV four-wire up to 1 kV
until 3 6 10
6 - 55 45 - - -
10 95 75 60 55 - 60
16 120 95 80 65 60 80
25 160 130 105 90 85 100
35 200 150 125 110 105 120
50 245 185 155 145 135 145
70 305 225 200 175 165 185
95 360 275 245 215 200 215
120 415 320 285 250 240 260
150 470 375 330 290 270 300
185 525 - 375 325 305 340
240 610 - 430 375 350 -
300 720 - - - - -
400 880 - - - - -
500 1020 - - - - -
625 1180 - - - - -
800 1400 - - - - -

Table 1.3.16. Permissible continuous current for cables with aluminum conductors with paper impregnated with oil rosin and non-drip insulation in a lead or aluminum sheath, laid in the ground

Conductor cross-section, mm² Current, A, for cables
single-core up to 1 kV two-wire up to 1 kV three-wire voltage, kV four-wire up to 1 kV
until 3 6 10
6 - 60 55 - - -
10 110 80 75 60 - 65
16 135 110 90 80 75 90
25 180 140 125 105 90 115
35 220 175 145 125 115 135
50 275 210 180 155 140 165
70 340 250 220 190 165 200
95 400 290 260 225 205 240
120 460 335 300 260 240 270
150 520 385 335 300 275 305
185 580 - 380 340 310 345
240 675 - 440 390 355 -
300 770 - - - - -
400 940 - - - - -
500 1080 - - - - -
625 1170 - - - - -
800 1310 - - - - -

Table 1.3.17. Permissible continuous current for cables with aluminum conductors with paper impregnated with oil rosin and non-drip insulation in a lead sheath, laid in water

Conductor cross-section, mm² Current, A, for cables
three-wire voltage, kV four-wire up to 1 kV
until 3 6 10
16 - 105 90 -
25 160 130 115 150
35 190 160 140 175
50 235 195 170 220
70 290 240 210 270
95 340 290 260 315
120 390 330 305 360
150 435 385 345 -
185 475 420 390 -
240 550 480 450 -

Table 1.3.18. Permissible continuous current for cables with aluminum conductors with paper impregnated with oil rosin and non-drip insulation in a lead or aluminum sheath, laid in the air

Conductor cross-section, mm² Current, A, for cables
single-core up to 1 kV two-wire up to 1 kV three-wire voltage, kV four-wire up to 1 kV
until 3 6 10
6 - 42 35 - - -
10 75 55 46 42 - 45
16 90 75 60 50 46 60
25 125 100 80 70 65 75
35 155 115 95 85 80 95
50 190 140 120 110 105 110
70 235 175 155 135 130 140
95 275 210 190 165 155 165
120 320 245 220 190 185 200
150 360 290 255 225 210 230
185 405 - 290 250 235 260
240 470 - 330 290 270 -
300 555 - - - - -
400 675 - - - - -
500 785 - - - - -
625 910 - - - - -
800 1080 - - - - -

Table 1.3.19. Permissible continuous current for three-core cables with a voltage of 6 kV with copper conductors with lean insulation in a common lead sheath, laid in the ground and air

Table 1.3.20. Permissible continuous current for three-core cables with a voltage of 6 kV with aluminum conductors with lean insulation in a common lead sheath, laid in the ground and air

Table 1.3.21. Permissible long-term current for cables with separately leaded copper conductors with paper impregnated with oil rosin and non-drip insulation, laid in the ground, water, air

Conductor cross-section, mm²
20 35
when laying
in the ground in water in the air in the ground in water in the air
25 110 120 85 - - -
35 135 145 100 - - -
50 165 180 120 - - -
70 200 225 150 - - -
95 240 275 180 - - -
120 275 315 205 270 290 205
150 315 350 230 310 - 230
185 355 390 265 - - -

Table 1.3.22. Permissible long-term current for cables with separately leaded aluminum conductors with paper impregnated with oil-rosin and non-drip insulation, laid in the ground, water, air

Conductor cross-section, mm² Current, A, for three-core cables with voltage, kV
20 35
when laying
in the ground in water in the air in the ground in water in the air
25 85 90 65 - - -
35 105 110 75 - - -
50 125 140 90 - - -
70 155 175 115 - - -
95 185 210 140 - - -
120 210 245 160 210 225 160
150 240 270 175 240 - 175
185 275 300 205 - - -

Table 1.3.23. Correction factor for permissible continuous current for cables laid in the ground, depending on the resistivity of the earth

If the earth resistivity differs from 120 cm K/W, it is necessary to apply the correction factors indicated in the table to the current loads indicated in the previously mentioned tables. 1.3.23.

1.3.14. For cables laid in water, permissible continuous currents are given in table. 1.3.14, 1.3.17, 1.3.21, 1.3.22. They are taken based on water temperature +15°C.

1.3.15. For cables laid in the air, inside and outside buildings, with any number of cables and an air temperature of +25°C, the permissible continuous currents are given in table. 1.3.15, 1.3.18-1.3.22, 1.3.24, 1.3.25.

1.3.16. Permissible long-term currents for single cables laid in pipes in the ground must be taken as for the same cables laid in the air, at a temperature equal to the temperature of the ground.

Table 1.3.24. Permissible continuous current for single-core cables with a copper conductor with paper impregnated with oil rosin and non-drip insulation in a lead sheath, unarmoured, laid in the air

Conductor cross-section, mm²
until 3 20 35
__________________
10 85/- - -
16 120/- - -
25 145/- 105/110 -
35 170/- 125/135 -
50 215/- 155/165 -
70 260/- 185/205 -
95 305/- 220/255 -
120 330/- 245/290 240/265
150 360/- 270/330 265/300
185 385/- 290/360 285/335
240 435/- 320/395 315/380
300 460/- 350/425 340/420
400 485/- 370/450 -
500 505/- - -
625 525/- - -
800 550/- - -

1.3.17. When laying mixed cables, permissible long-term currents must be taken for the section of the route with the worst cooling conditions, if its length is more than 10 m. It is recommended to use cable inserts with a larger cross-section in these cases.

1.3.18. When laying several cables in the ground (including laying in pipes), the permissible continuous currents must be reduced by introducing the coefficients given in table. 1.3.26. This does not include redundant cables.

Laying multiple cables in the ground with clear distances between them of less than 100 mm is not recommended.

1.3.19. For oil- and gas-filled single-core armored cables, as well as other cables of new designs, permissible continuous currents are established by the manufacturers.

1.3.20. Permissible long-term currents for cables laid in blocks should be determined using the empirical formula

I = abcI0,

Where I0- permissible continuous current for a three-core cable with a voltage of 10 kV with copper or aluminum conductors, determined according to table. 1.3.27; a- coefficient selected according to the table. 1.3.28 depending on the cross-section and location of the cable in the block; b- coefficient selected depending on the cable voltage:

c- coefficient selected depending on the average daily load of the entire block:

1 0,85 0,7

Coefficient c

1 1,07 1,16

Table 1.3.25. Permissible continuous current for single-core cables with an aluminum core with paper impregnated with oil rosin and non-drip insulation in a lead or aluminum sheath, unarmoured, laid in the air

Current *, A, for cables with voltage, kV
until 3 20 35
__________________

* The numerator indicates currents for cables located in the same plane with a clear distance of 35-125 mm, the denominator indicates currents for cables located closely in a triangle.

10 65/- - -
16 90/- - -
25 110/- 80/85 -
35 130/- 95/105 -
50 165/- 120/130 -
70 200/- 140/160 -
95 235/- 170/195 -
120 255/- 190/225 185/205
150 275/- 210/255 205/230
185 295/- 225/275 220/255
240 335/- 245/305 245/290
300 355/- 270/330 260/330
400 375/- 285/350 -
500 390/- - -
625 405/- - -
800 425/- - -

Table 1.3.26. Correction factor for the number of working cables lying nearby in the ground (in pipes or without pipes)

Table 1.3.27. Permissible continuous current for cables, kV with copper or aluminum conductors with a cross-section of 95 mm², laid in blocks

Group Block configuration Channel no. Current I, And for cables
copper aluminum
I 1 191 147
II 2 173 133
3 167 129
III 2 154 119
IV 2 147 113
3 138 106
V 2 143 110
3 135 104
4 131 101
VI 2 140 103
3 132 102
4 118 91
VII 2 136 105
3 132 102
4 119 92
VIII 2 135 104
3 124 96
4 104 80
IX 2 135 104
3 118 91
4 100 77
X 2 133 102
3 116 90
4 81 62
XI 2 129 99
3 114 88
4 79 55

Table 1.3.28. Correction factor a per cable cross section

Conductor cross-section, mm2 Coefficient for the channel number in the block
1 2 3 4
25 0,44 0,46 0,47 0,51
35 0,54 0,57 0,57 0,60
50 0,67 0,69 0,69 0,71
70 0,81 0,84 0,84 0,85
95 1,00 1,00 1,00 1,00
120 1,14 1,13 1,13 1,12
150 1,33 1,30 1,29 1,26
185 1,50 1,46 1,45 1,38
240 1,78 1,70 1,68 1,55

Backup cables may be laid in unnumbered channels of the unit if they work when the working cables are disconnected.

1.3.21. Permissible continuous currents for cables laid in two parallel blocks of the same configuration must be reduced by multiplying by coefficients selected depending on the distance between the blocks:

Permissible continuous currents for bare wires and buses

1.3.22. Permissible continuous currents for bare wires and painted tires are given in table. 1.3.29-1.3.35. They are taken based on the permissible heating temperature of +70°C at an air temperature of +25°C.

For hollow aluminum wires of grades PA500 and PA600, the permissible continuous current should be taken:

Wire brand

PA500 Pa6000
1340 1680

1.3.23. When rectangular busbars are arranged flat, the currents given in table. 1.3.33, must be reduced by 5% for tires with a stripe width of up to 60 mm and by 8% for tires with a stripe width of more than 60 mm.

1.3.24. When choosing buses of large sections, it is necessary to choose the most economical design solutions in terms of throughput, ensuring the least additional losses from the surface effect and the proximity effect and the best cooling conditions (reducing the number of strips in the package, rational design of the package, the use of profile tires, etc.) .

Table 1.3.29. Permissible continuous current for bare wires according to GOST 839-80

Nominal cross-section, mm² Section (aluminium/steel), mm2 Current, A, for wire brands
AS, ASKS, ASK, ASKP M A and automatic transmission M A and automatic transmission
outdoors indoors outdoors indoors
10 10/1,8 84 53 95 - 60 -
16 16/2,7 111 79 133 105 102 75
25 25/4,2 142 109 183 136 137 106
35 35/6,2 175 135 223 170 173 130
50 50/8 210 165 275 215 219 165
70 70/11 265 210 337 265 268 210
95 95/16 330 260 422 320 341 255
120 120/19 390 313 485 375 395 300
120/27 375 -
150 150/19 450 365 570 440 465 355
150/24 450 365
150/34 450 -
185 185/24 520 430 650 500 540 410
185/29 510 425
185/43 515 -
240 240/32 605 505 760 590 685 490
240/39 610 505
240/56 610 -
300 300/39 710 600 880 680 740 570
300/48 690 585
300/66 680 -
330 330/27 730 - - - - -
400 400/22 830 713 1050 815 895 690
400/51 825 705
400/64 860 -
500 500/27 960 830 - 980 - 820
500/64 945 815
600 600/72 1050 920 - 1100 - 955
700 700/86 1180 1040 - - - -

Table 1.3.30. Permissible continuous current for round and tubular busbars

Diam, mm Round tires Copper pipes Aluminum pipes Steel pipes
Current *, A Int. and external dia., mm Current, A Int. and external dia., mm Current, A Conditional passage, mm Thickness walls, mm External diameter, mm Alternating current, A
copper aluminum without incision with extended cut
__________________

* The numerator shows loads with alternating current, the denominator shows loads with direct current.

6 155/155 120/120 12/15 340 13/16 295 8 2,8 13,5 75 -
7 195/195 150/150 14/18 460 17/20 345 10 2,8 17,0 90 -
8 235/235 180/180 16/20 505 18/22 425 15 3,2 21.3 118 -
10 320/320 245/245 18/22 555 27/30 500 20 3,2 26,8 145 -
12 415/415 320/320 20/24 600 26/30 575 25 4,0 33,5 180 -
14 505/505 390/390 22/26 650 25/30 640 32 4,0 42,3 220 -
15 565/565 435/435 25/30 830 36/40 765 40 4,0 48,0 255 -
16 610/615 475/475 29/34 925 35/40 850 50 4,5 60,0 320 -
18 720/725 560/560 35/40 1100 40/45 935 65 4,5 75,5 390 -
19 780/785 605/610 40/45 1200 45/50 1040 80 4,5 88,5 455 -
20 835/840 650/655 45/50 1330 50/55 1150 100 5,0 114 670 770
21 900/905 695/700 49/55 1580 54/60 1340 125 5,5 140 800 890
22 955/965 740/745 53/60 1860 64/70 1545 150 5,5 165 900 1000
25 1140/1165 885/900 62/70 2295 74/80 1770 - - - - -
27 1270/1290 980/1000 72/80 2610 72/80 2035 - - - - -
28 1325/1360 1025/1050 75/85 3070 75/85 2400 - - - - -
30 1450/1490 1120/1155 90/95 2460 90/95 1925 - - - - -
35 1770/1865 1370/1450 95/100 3060 90/100 2840 - - - - -
38 1960/2100 1510/1620 - - - - - - - - -
40 2080/2260 1610/1750 - - - - - - - - -
42 2200/2430 1700/1870 - - - - - - - - -
45 2380/2670 1850/2060 - - - - - - - - -

Table 1.3.31. Permissible continuous current for rectangular busbars

Size, mm Copper bars Aluminum tires Steel tires
Current *, A, with the number of stripes per pole or phase Size, mm Current *, A
1 2 3 4 1 2 3 4
__________________

* The numerator shows the values ​​of alternating current, the denominator shows the values ​​of direct current.

15x3 210 - - - 165 - - - 16x2.5 55/70
20x3 275 - - - 215 - - - 20x2.5 60/90
25x3 340 - - - 265 - - - 25x2.5 75/110
30x4 475 - - - 365/370 - - - 20x3 65/100
40x4 625 -/1090 - - 480 -/855 - - 25x3 80/120
40x5 700/705 -/1250 - - 540/545 -/965 - - 30x3 95/140
50x5 860/870 -/1525 -/1895 - 665/670 -/1180 -/1470 - 40x3 125/190
50x6 955/960 -/1700 -/2145 - 740/745 -/1315 -/1655 - 50x3 155/230
60x6 1125/1145 1740/1990 2240/2495 - 870/880 1350/1555 1720/1940 - 60x3 185/280
80x6 1480/1510 2110/2630 2720/3220 - 1150/1170 1630/2055 2100/2460 - 70x3 215/320
100x6 1810/1875 2470/3245 3170/3940 - 1425/1455 1935/2515 2500/3040 - 75x3 230/345
60x8 1320/1345 2160/2485 2790/3020 - 1025/1040 1680/1840 2180/2330 - 80x3 245/365
80x8 1690/1755 2620/3095 3370/3850 - 1320/1355 2040/2400 2620/2975 - 90x3 275/410
100x8 2080/2180 3060/3810 3930/4690 - 1625/1690 2390/2945 3050/3620 - 100x3 305/460
120x8 2400/2600 3400/4400 4340/5600 - 1900/2040 2650/3350 3380/4250 - 20x4 70/115
60x10 1475/1525 2560/2725 3300/3530 - 1155/1180 2010/2110 2650/2720 - 22x4 75/125
80x10 1900/1990 3100/3510 3990/4450 - 1480/1540 2410/2735 3100/3440 - 25x4 85/140
100x10 2310/2470 3610/4325 4650/5385 5300/ 6060 1820/1910 2860/3350 3650/4160 4150/ 4400 30x4 100/165
120x10 2650/2950 4100/5000 5200/6250 5900/ 6800 2070/2300 3200/3900 4100/4860 4650/ 5200 40x4 130/220
- 50x4 165/270
60x4 195/325
70x4 225/375
80x4 260/430
90x4 290/480
100x4 325/535

Table 1.3.32. Permissible continuous current for uninsulated bronze and steel-bronze wires

Table 1.3.33. Permissible continuous current for bare steel wires

Wire brand Current, A Wire brand Current, A
PSO-3 23 PS-25 60
PSO-3.5 26 PS-35 75
PSO-4 30 PS-50 90
PSO-5 35 PS-70 125
- PS-95 135

Table 1.3.34. Permissible continuous current for four-lane buses with stripes arranged on the sides of a square ("hollow package")

Dimensions, mm Cross section of a four-lane tire, mm² Current, A, per bus package
h b h1 H copper aluminum
80 8 140 157 2560 5750 4550
80 10 144 160 3200 6400 5100
100 8 160 185 3200 7000 5550
100 10 164 188 4000 7700 6200
120 10 184 216 4800 9050 7300

Table 1.3.35. Permissible continuous current for box-section busbars

Dimensions, mm Cross section of one tire, mm² Current, A, for two buses
a b c r copper aluminum
75 35 4 6 520 2730 -
75 35 5,5 6 695 3250 2670
100 45 4,5 8 775 3620 2820
100 45 6 8 1010 4300 3500
125 55 6,5 10 1370 5500 4640
150 65 7 10 1785 7000 5650
175 80 8 12 2440 8550 6430
200 90 10 14 3435 9900 7550
200 90 12 16 4040 10500 8830
225 105 12,5 16 4880 12500 10300
250 115 12,5 16 5450 - 10800

Selection of wire cross-section based on economic current density

1.3.25. Conductor cross-sections must be checked for economic current density. Economically feasible section S, mm², is determined from the relation

S = I / Jek,

Where I- calculated current per hour of maximum power system, A; Jack- normalized value of economic current density, A/mm², for given operating conditions, selected according to table. 1.3.36.

The section obtained as a result of the specified calculation is rounded to the nearest standard section. The calculated current is taken for normal operation, i.e. the increase in current in post-emergency and repair modes of the network is not taken into account.

1.3.26. The selection of wire cross-sections for direct and alternating current power lines with voltages of 330 kV and above, as well as interconnection lines and powerful rigid and flexible conductors operating with a large number of hours of maximum use, is made on the basis of technical and economic calculations.

1.3.27. An increase in the number of lines or circuits beyond what is required under the conditions of reliability of power supply in order to satisfy the economic current density is carried out on the basis of a technical and economic calculation. In this case, in order to avoid increasing the number of lines or circuits, it is allowed to exceed the normalized values ​​given in table two times. 1.3.36.

1,6

Feasibility calculations should take into account all investments in an additional line, including equipment and switchgear chambers at both ends of the lines. The feasibility of increasing the line voltage should also be checked.

These guidelines should also be followed when replacing existing wires with wires of larger cross-section or when laying additional lines to ensure economical current density as the load increases. In these cases, the full cost of all work on dismantling and installing line equipment, including the cost of apparatus and materials, must also be taken into account.

1.3.28. The following are not subject to verification by economic current density:

networks of industrial enterprises and structures with voltage up to 1 kV with the number of hours of use of the maximum load of enterprises up to 4000-5000;

branches to individual electrical receivers with voltages up to 1 kV, as well as lighting networks of industrial enterprises, residential and public buildings;

busbars of electrical installations and busbars within open and closed switchgears of all voltages;

conductors going to resistors, starting rheostats, etc.;

networks of temporary structures, as well as devices with a service life of 3-5 years.

1.3.29. When using the table. 1.3.36 the following must be followed (see also 1.3.27):

1. At maximum load at night, the economic current density increases by 40%.

2. For insulated conductors with a cross-section of 16 mm² or less, the economic current density increases by 40%.

3. For lines of the same section with n branch loads, the economic current density at the beginning of the line can be increased by kp times, and kp determined from the expression

,

Where I1, I2, ..., In- loads of individual sections of the line; l1, l2, ..., ln- lengths of individual sections of the line; L- total line length.

4. When choosing conductor cross-sections for power supply n similar, mutually redundant electrical receivers (for example, water supply pumps, converter units, etc.), of which m are in operation at the same time, the economic current density can be increased against the values ​​​​given in table. 1.3.36, in kn times where kn equals:

1.3.30. The cross-section of 35 kV overhead line wires in rural areas feeding step-down substations 35/6 - 10 kV with transformers with voltage regulation under load should be selected according to the economic current density. It is recommended to take the design load when choosing wire sections for a 5-year perspective, counting from the year the overhead line was put into operation. For 35 kV overhead lines intended for redundancy in 35 kV networks in rural areas, the minimum long-term permissible current wire cross-sections should be used, based on the provision of power to electricity consumers in post-emergency and repair modes.

1.3.31. The choice of economic cross-sections of overhead wires and cores of cable lines with intermediate power take-offs should be made for each section, based on the corresponding calculated currents of the sections. In this case, for neighboring sections it is allowed to take the same wire cross-section corresponding to the economic cross-section for the longest section, if the difference between the values ​​of the economic cross-section for these sections is within one step on the scale of standard sections. The cross-sections of wires on branches up to 1 km in length are taken to be the same as on the overhead line from which the branch is made. With a longer branch length, the economic cross-section is determined by the design load of this branch.

1.3.32. For power lines with voltage 6-20 kV given in table. 1.3.36 current density values ​​may be used only when they do not cause voltage deviations at electricity receivers beyond permissible limits, taking into account the applied means of voltage regulation and reactive power compensation.

CHECKING CONDUCTORS FOR CORONA AND RADIO INTERFERENCE

1.3.33. At voltages of 35 kV and above, conductors must be checked for the conditions of corona formation, taking into account the average annual values ​​of density and air temperature at the height of the electrical installation above sea level, the reduced radius of the conductor, as well as the coefficient of roughness of the conductors.

In this case, the highest field strength at the surface of any of the conductors, determined at the average operating voltage, should be no more than 0.9 of the initial electric field strength, corresponding to the appearance of a common corona.

The test should be carried out in accordance with current guidelines.

In addition, conductors must be tested according to the permissible level of radio interference from corona.

The table shows power, current and cross sections of cables and wires, For calculations and selection of cables and wires, cable materials and electrical equipment.


The calculation used data from the PUE tables and active power formulas for single-phase and three-phase symmetrical loads.


Below are tables for cables and wires with copper and aluminum wire cores.

Table for selecting cable cross-section for current and power with copper conductors
Copper conductors of wires and cables
Voltage, 220 V Voltage, 380 V
current, A power, kWt current, A power, kWt
1,5 19 4,1 16 10,5
2,5 27 5,9 25 16,5
4 38 8,3 30 19,8
6 46 10,1 40 26,4
10 70 15,4 50 33,0
16 85 18,7 75 49,5
25 115 25,3 90 59,4
35 135 29,7 115 75,9
50 175 38,5 145 95,7
70 215 47,3 180 118,8
95 260 57,2 220 145,2
120 300 66,0 260 171,6
Table for selecting cable cross-section for current and power with aluminum conductors
Cross-section of current-carrying conductor, mm 2 Aluminum conductors of wires and cables
Voltage, 220 V Voltage, 380 V
current, A power, kWt current, A power, kWt
2,5 20 4,4 19 12,5
4 28 6,1 23 15,1
6 36 7,9 30 19,8
10 50 11,0 39 25,7
16 60 13,2 55 36,3
25 85 18,7 70 46,2
35 100 22,0 85 56,1
50 135 29,7 110 72,6
70 165 36,3 140 92,4
95 200 44,0 170 112,2
120 230 50,6 200 132,0

Example of cable cross-section calculation

Task: to power the heating element with a power of W=4.75 kW with copper wire in the cable channel.
Current calculation: I = W/U. We know the voltage: 220 volts. According to the formula, the flowing current I = 4750/220 = 21.6 amperes.

We focus on copper wire, so we take the value of the diameter of the copper core from the table. In the 220V - copper conductors column we find a current value exceeding 21.6 amperes, this is a line with a value of 27 amperes. From the same line we take the cross-section of the conductive core, equal to 2.5 squares.

Calculation of the required cable cross-section based on the type of cable or wire

Number of veins
section mm.
Cables (wires)
Outer diameter mm. Pipe diameter mm. Acceptable long
current (A) for wires and cables when laying:
Permissible continuous current
for rectangular copper bars
sections (A) PUE
VVG VVGng KVVG KVVGE NYM PV1 PV3 PVC (HDPE) Met.tr. Du in the air in the ground Section, tires mm Number of buses per phase
1 1x0.75 2,7 16 20 15 15 1 2 3
2 1x1 2,8 16 20 17 17 15x3210
3 1x1.55,4 5,4 3 3,2 16 20 23 33 20x3275
4 1x2.55,4 5,7 3,5 3,6 16 20 30 44 25x3340
5 1x46 6 4 4 16 20 41 55 30x4475
6 1x66,5 6,5 5 5,5 16 20 50 70 40x4625
7 1x107,8 7,8 5,5 6,2 20 20 80 105 40x5700
8 1x169,9 9,9 7 8,2 20 20 100 135 50x5860
9 1x2511,5 11,5 9 10,5 32 32 140 175 50x6955
10 1x3512,6 12,6 10 11 32 32 170 210 60x61125 1740 2240
11 1x5014,4 14,4 12,5 13,2 32 32 215 265 80x61480 2110 2720
12 1x7016,4 16,4 14 14,8 40 40 270 320 100x61810 2470 3170
13 1x9518,8 18,7 16 17 40 40 325 385 60x81320 2160 2790
14 1x12020,4 20,4 50 50 385 445 80x81690 2620 3370
15 1x15021,1 21,1 50 50 440 505 100x82080 3060 3930
16 1x18524,7 24,7 50 50 510 570 120x82400 3400 4340
17 1x24027,4 27,4 63 65 605 60x101475 2560 3300
18 3x1.59,6 9,2 9 20 20 19 27 80x101900 3100 3990
19 3x2.510,5 10,2 10,2 20 20 25 38 100x102310 3610 4650
20 3x411,2 11,2 11,9 25 25 35 49 120x102650 4100 5200
21 3x611,8 11,8 13 25 25 42 60
rectangular copper bars
(A) Schneider Electric IP30
22 3x1014,6 14,6 25 25 55 90
23 3x1616,5 16,5 32 32 75 115
24 3x2520,5 20,5 32 32 95 150
25 3x3522,4 22,4 40 40 120 180 Section, tires mm Number of buses per phase
26 4x1 8 9,5 16 20 14 14 1 2 3
27 4x1.59,8 9,8 9,2 10,1 20 20 19 27 50x5650 1150
28 4x2.511,5 11,5 11,1 11,1 20 20 25 38 63x5750 1350 1750
29 4x5030 31,3 63 65 145 225 80x51000 1650 2150
30 4x7031,6 36,4 80 80 180 275 100x51200 1900 2550
31 4x9535,2 41,5 80 80 220 330 125x51350 2150 3200
32 4x12038,8 45,6 100 100 260 385 Permissible continuous current for
rectangular copper bars (A) Schneider Electric IP31
33 4x15042,2 51,1 100 100 305 435
34 4x18546,4 54,7 100 100 350 500
35 5x1 9,5 10,3 16 20 14 14
36 5x1.510 10 10 10,9 10,3 20 20 19 27 Section, tires mm Number of buses per phase
37 5x2.511 11 11,1 11,5 12 20 20 25 38 1 2 3
38 5x412,8 12,8 14,9 25 25 35 49 50x5600 1000
39 5x614,2 14,2 16,3 32 32 42 60 63x5700 1150 1600
40 5x1017,5 17,5 19,6 40 40 55 90 80x5900 1450 1900
41 5x1622 22 24,4 50 50 75 115 100x51050 1600 2200
42 5x2526,8 26,8 29,4 63 65 95 150 125x51200 1950 2800
43 5x3528,5 29,8 63 65 120 180
44 5x5032,6 35 80 80 145 225
45 5x9542,8 100 100 220 330
46 5x12047,7 100 100 260 385
47 5x15055,8 100 100 305 435
48 5x18561,9 100 100 350 500
49 7x1 10 11 16 20 14 14
50 7x1.5 11,3 11,8 20 20 19 27
51 7x2.5 11,9 12,4 20 20 25 38
52 10x1 12,9 13,6 25 25 14 14
53 10x1.5 14,1 14,5 32 32 19 27
54 10x2.5 15,6 17,1 32 32 25 38
55 14x1 14,1 14,6 32 32 14 14
56 14x1.5 15,2 15,7 32 32 19 27
57 14x2.5 16,9 18,7 40 40 25 38
58 19x1 15,2 16,9 40 40 14 14
59 19x1.5 16,9 18,5 40 40 19 27
60 19x2.5 19,2 20,5 50 50 25 38
61 27x1 18 19,9 50 50 14 14
62 27x1.5 19,3 21,5 50 50 19 27
63 27x2.5 21,7 24,3 50 50 25 38
64 37x1 19,7 21,9 50 50 14 14
65 37x1.5 21,5 24,1 50 50 19 27
66 37x2.5 24,7 28,5 63 65 25 38